Datalogic M-Series Manuel d'instructions Page 102

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 134
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 101
M1xx Camera Connection (Older Terminal Blocks) M-Series Processor and Camera Guide
Datalogic Automation, Inc. 6-2
NOTE: The M1xx camera's Strobe Trigger Out is normally closed (it opens to trigger the strobe). Do not wire multiple
cameras' strobe outputs in parallel to trigger a single strobe.
To connect the power cable to the camera, align the cable connector with the connector on the rear of the camera, push
gently until the cable connector seats securely, then tighten the connector collar. To disconnect it, loosen the collar com-
pletely, then grasp the connector and gently pull.
NOTE: To reduce stress on the cable and connectors, loop the cable and fasten it to the camera's mounting block. Do not
crimp or tie the cable tightly with wire ties as this may damage it internally. The cable is not intended for continuous flex-
ing or movement. The cable's maximum bend radius is fifteen times the cable diameter.
Vue de la page 101
1 2 ... 97 98 99 100 101 102 103 104 105 106 107 ... 133 134

Commentaires sur ces manuels

Pas de commentaire