Page 1 - Reference Manual

DS6300Reference Manual

Page 2

DS6300 2 1 Figure B - DS6300 Oscillating Mirror Version Laser Safety Label1Laser Beam Output Window2 41 235 Figure C - Display and Keyp

Page 3 - CONTENTS

Interface A shared boundary defined by common physical interconnection characteristics, signal characteristics and meanings of interchanged signals.

Page 4

Skew Rotation about the Y-axis. Rotational deviation from correct horizontal and vertical orientation; may apply to single character, line or entire

Page 5 - REFERENCES

INDEX A Accessories; 6 ACR™ 4; 65 C CE Compliance; vii Cleaning; 78 Connectors 25-pin connector; 17 26-pin connector; 17 DeviceNet; 32 Ethernet; 30

Page 6 - COMPLIANCE

R Reading Diagrams; 68 DS6300 with GFX-60; 76 Oscillating Mirror Models; 72 Standard Models; 68 Reading Features; 65 Reference Documentation; v S Sca

Page 7 - WEEE COMPLIANCE

DECLARATION OF CONFORMITY 07Datalogic Automation S.r.l. Via S. Vitalino 13 40012 - Lippo di Calderara Bologna - Italy dichiara che declares that

Page 8

www.automation.datalogic.com

Page 9 - GENERAL VIEW

3 2 1 Figure D - Connector Panel for Master/Slave Models nnector Main/Aux. Interface 25-pin D-Sub male co1 Lonworks 9-pin male connector2 Lonworks

Page 10 - Laser Beam Output Window

GUIDE TO INSTALLATION POINT-TO-POINT INSTALLATION The following can be used as a checklist to verify all the steps necessary to complete installat

Page 11

MASTER/SLAVE LONWORKS INSTALLATION The following can be used as a checklist to verify all the steps necessary to complete installation of the DS6300

Page 12 - GUIDE TO INSTALLATION

8) Optionally, perform the ASR Network Configuration procedure for system backup purposes (see par. 5.2.1). 9) Exit the configuration program and r

Page 13

INTRODUCTION 11 INTRODUCTION 1.1 PRODUCT DESCRIPTION The DS6300 is the first high performance laser scanner in a complete range of industrial barco

Page 14

DS6300 1 The DS6300 features have been defined to give a set of benefits answering the main manufacturing industry needs . Features Benefits Modular

Page 15 - 1 INTRODUCTION

INTRODUCTION 11.3 OSCILLATING MIRROR MODELS Oscillating mirror models are used when coverage of a large reading area is required, mainly in picket fe

Page 16 - DS6300 - 10X - 0Y

DS6300 1 The mirror can be deflected up to 40°. Oscillation with respect to the output window median axis is asymmetrical ( see figure below). 40°

Page 17 - INTRODUCTION

INTRODUCTION 1The following example represents the selection of an angle of +10° for the bottom line and an angle of +20° for the top line (see figure

Page 18

Datalogic Automation S.r.l. Via S. Vitalino 13 40012 - Lippo di Calderara di Reno Bologna - Italy DS6300 Reference Manual Ed.: 10/2007

Page 19 - 1.4 INDICATORS

DS6300 1 1.5 ACCESSORIES The following accessories are available on request for DS6300: Name Description Part Number CAB-6001 cable to C-BOX100 1

Page 20 - 1.5 ACCESSORIES

INSTALLATION 22 INSTALLATION To install the system follow the given procedure: • Select the mounting location for DS6300; • Mount the DS6300 scann

Page 21 - 2 INSTALLATION

DS6300 2 2.2 MECHANICAL MOUNTING 2.2.1 Mounting the Scanner The DS6300 reader can be positioned and installed in the best way possible as a result

Page 22 - 2.2.1 Mounting the Scanner

INSTALLATION 2The following diagrams give the overall dimensions of the reader standard model, the oscillating mirror model and mounting brackets. The

Page 23 - INSTALLATION

DS6300 2 3.35 0.652.361.183.902.724.112.504.344.012.204.484.457.08mminch306085 16.5104.563.5699911311456110.3102180 Figure 10 - DS6300 Oscillating Mir

Page 24

INSTALLATION 22.2.2 Mounting the Scanner with Accessories The following accessories allow installing the DS6300 reader in the most suitable position

Page 25

DS6300 2 The FBK-6000 is a fast bracket kit allowing a quick and easy mounting of the scanner on either the ST-210 or the ST-237 brackets. First, it

Page 26

INSTALLATION 22.2.3 Mounting the Scanner with GFX-60 The GFX-60 is an X-pattern mirror for the DS6300 Series Scanners. The following procedure descr

Page 27

DS6300 2 6. Mount the scanner at an angle of 16°, as indicated in figure below, in order to obtain an angle of 90° between the two scan lines. This g

Page 28

INSTALLATION 22.3 ELECTRICAL CONNECTIONS All the connectors available for each scanner model are the following: Scanner Model Connector Master/Sla

Page 29 - 2.3 ELECTRICAL CONNECTIONS

CONTENTS REFERENCES ...v Reference Docume

Page 30 - (with INT-30 only)

DS6300 2 The table below gives the pinout of the C-BOX 100 terminal block connectors. Use this pinout when the DS6300 reader is connected in a network

Page 31 - (INT-30 with C-BOX 100 only)

INSTALLATION 22.3.1 Main/Aux. Serial Interface and I/O Connector The DS6300 master/slave model is equipped with a 25-pin male D-sub connector for co

Page 32 - RS232 Interface

DS6300 2 Main Interface The main serial interface is compatible with the following electrical standards: RS232 RS485 full-duplex RS485 half-duplex (

Page 33 - RS485 Full-Duplex Interface

INSTALLATION 2RS485 Full-Duplex Interface The RS485 full-duplex interface is used for non-polled communication protocols in point-to-point connectio

Page 34 - RS485 Half-Duplex Interface

DS6300 2 RS485 Half-Duplex Interface The RS485 half-duplex interface can be used for multidrop connections with a Datalogic multiplexer or it can als

Page 35 - Auxiliary Interface

INSTALLATION 2Auxiliary Interface The auxiliary serial interface is equipped with RS232 full-duplex interface connections. The interface type is excl

Page 36 - EXTERNAL TRIGGER/ENCODER

DS6300 2 Inputs The inputs of the reader are on the 25-pin and 26-pin connector (Figure D, 1 and Figure E, 1) of the DS6300. These inputs are called

Page 37

INSTALLATION 2 EXTERNAL TRIGGER/ENCODER DS6300 A/BVext B/AV+ 5V ~~+-Ground Figure 26 - NPN Command Input Connection using External Power EXTERNAL

Page 38 - Outputs

DS6300 2 EXTERNAL DEVICE DS6300 IN3AGroundV+ 5V ~~+-EXTERNAL DEVICE GND VIN4A+ 5V ~~+-INREFVSGround Figure 29 - IN3/IN4 NPN Input Command using Scanne

Page 39

INSTALLATION 2By default, OUT1 is associated with COMPLETE READ event, which activates when the code has been read correctly. In case the reader has b

Page 40 - Male (Master/Slave model)

2.8.2 Test Mode...51 2.9 Focus Adju

Page 41 - Network Termination

DS6300 2 DS6300 USER INTERFACEVext100 Vdc maxAB Figure 31 – Output 3 Interface The command signal is filtered and generates a delay of about 50 µs f

Page 42 - CAUTION

INSTALLATION 2 DS6300 9-pin Lonworks connector pinout Pin Name Function 1 CHASSIS Cable shield internally connected by capacitor to chassis 9 VS

Page 43

DS6300 2 Lonworks Interface The Lonworks network is used for both input and output connection to build a multi-sided or omni-station system connectin

Page 44 - 2.3.3 Ethernet Connector

INSTALLATION 2The diagram below represents the termination of a DS6300-XXX-010 working as master by means of the BTK-6000 terminator. MasterBTK-6000

Page 45 - Ethernet Interface

DS6300 2 2.3.3 Ethernet Connector This connector is only available for DS6300 Ethernet models and allows the Ethernet connection between the host and

Page 46 - 2.3.4 DeviceNet Connector

INSTALLATION 2Ethernet Interface The Ethernet interface (NIC) can be used for TCP/IP communication with remote or local host computer by connecting t

Page 47 - Profibus Interface

DS6300 2 2.3.4 DeviceNet Connector NOTE When using DeviceNet, the Main serial interface is disabled and must not be physically connected. The 5-pin

Page 48 - 2.4 USER INTERFACE

INSTALLATION 22.3.5 Profibus Connector The 9-pin female Profibus connector (white) is only available in the DS6300 Profibus model and allows connecti

Page 49 - 2.5 POSITIONING THE SCANNER

DS6300 2 2.3.6 Power Supply The supply voltage of a single scanner must be between 15 and 30 VDC. Datalogic strongly recommends a minimum 24 VDC sup

Page 50

INSTALLATION 2How To Build A Simple Interface Test Cable: The following wiring diagram shows a simple test cable including power, external (push-but

Page 51 - 2.6.1 Standard Installation

REFERENCES REFERENCE DOCUMENTATION The documentation related to the DS6300 management is listed below: • C-BOX Installation Manual • INT-30 20 m

Page 52 - 2.7.1 Point-to-Point

DS6300 2 The Skew angle is represented by the value S in Figure 47. Position the reader to assure at least 10° for the Skew angle. This avoids the dir

Page 53 - Fieldbus

INSTALLATION 22.6 TYPICAL INSTALLATIONS 2.6.1 Standard Installation The DS6300 scanner is mounted on the ST-237 106° mounting bracket (see Figure 9)

Page 54 - 2.7.2 Pass Through

DS6300 2 ATTENTION If using the “45° Skew” installation, the scanner reading performance is not guaranteed to match that measured for the standard i

Page 55 - CAB-601X

INSTALLATION 2Master/Slave Models When On-Line operating mode is used, the reader is activated by an External Trigger (photoelectric sensor) when the

Page 56

DS6300 2 2.7.2 Pass Through When Pass Through is activated on the Auxiliary interface, the DS6300 reader (all models) can be integrated in a network

Page 57 - 2.7.4 Multiplexer

INSTALLATION 2 ENT<<ENT<< 1 2 Main Serial InterfaceAuxiliary Serial Interface * P.S. (Presence Sensor) connected to External Trigger/

Page 58 - 2.7.5 Local Lonworks Network

DS6300 2 ENT<<ENT<< 1 2 Main Serial Interface Auxiliary Serial Interface P.S.*AUXDS6300- MasterC-BOX 100Local Host PWR-120C-BOX 100 C-B

Page 59 - Small Synchronized Network

INSTALLATION 22.7.4 Multiplexer The Multiplexer connection is used to integrate a DS6300 slave reader in a Multidrop network consisting of different

Page 60

DS6300 2 2.7.5 Local Lonworks Network A local Lonworks network allows logically connecting a DS6300 master reader with up to 31 DS6300 slaves. Actual

Page 61 - Large Synchronized Network

INSTALLATION 2Small Synchronized Network When building a small local Lonworks network (less than 10 scanners), the DS6300 master reader must be conne

Page 62 - Multidata Network

COMPLIANCE ELECTRICAL SAFETY This product conforms to the applicable requirements contained in the European Standard for electrical safety EN-6095

Page 63

DS6300 2 The following image shows a system consisting of six readers where: • the system is powered by the PWR-240 • the master and all slaves are

Page 64 - 2.8.1 Internal Net

INSTALLATION 2Large Synchronized Network When building a large local Lonworks network (more than 10 scanners), an SC6000 Controller must be used toge

Page 65 - 2.9 FOCUS ADJUSTMENT

DS6300 2 Multidata Network In this layout, one master and up to 7 DS6300 slave readers have their own P.S. and therefore multiple reading phases. Eac

Page 66 -

INSTALLATION 22.7.6 Fieldbus Network The Fieldbus Ethernet model offers connectivity without any converter or adapter needed. The DS6300 master Fie

Page 67 - 3 SOFTWARE CONFIGURATION

DS6300 2 2.8 KEYPAD AND DISPLAY The DS6300 keypad allows entering a menu for selection of one of the following functions: • Welcome: shows the curre

Page 68 - Test Oper

INSTALLATION 22.8.2 Test Mode Test Mode is particularly advised during the installation phase, since it causes the reader to be continuously activate

Page 69 - Automatic Operating Mode

DS6300 2 Display Visualization The first line of the display shows the read code and Good Read percentage. Possible suspending commas at the end of th

Page 70

SOFTWARE CONFIGURATION 33 SOFTWARE CONFIGURATION 3.1 GENIUS™ INSTALLATION Genius™ is a new Datalogic scanner configuration tool providing several i

Page 71 - SOFTWARE CONFIGURATION

DS6300 3 After defining the parameter values the following window appears allowing to complete the reader configuration as follows: - Saving the conf

Page 72 - Net-Autoset

SOFTWARE CONFIGURATION 3On Line Operating Mode Figure 69 - On Line Mode Selection This operating mode requires the reader to be connected to an ext

Page 73 - Network Wizard

The identification label is applied onto the bottom part of the scanner (Figure A, 2): N2468DATALOGIC S.p.A. Via Candini, 2 40012 LIPPO DI CALDERARA

Page 74

DS6300 3 3.2.2 Genius™ Network Setup Through Master The Network Setup allows configuring your Local Lonworks Network through the Master using Genius

Page 75

SOFTWARE CONFIGURATION 3The following dialog box appears asking whether to send the configuration to the Master or not: 2. Click the "Yes&quo

Page 76 - 3.4 PARAMETER DEFAULT VALUES

DS6300 3 3. Then, proceed with the network setup by using one of the icons available on the Tool Bar according to the procedure to follow: = Net-Au

Page 77

SOFTWARE CONFIGURATION 3Network Wizard Before performing this procedure, a Lonworks address must be assigned to each slave scanner. The most practica

Page 78

DS6300 3 2. If desired, select a slave scanner within the "Current Devices" area and click on the icon (or select the "Show Device&quo

Page 79 - 4 READING FEATURES

SOFTWARE CONFIGURATION 33.2.3 Alternative Slave Address Assignment As alternatives to Network Setup through the Master, each Slave scanner can be ass

Page 80 - Laser Beam

DS6300 3 3.4 PARAMETER DEFAULT VALUES The following table contains the list of the factory default settings for the DS6300. Genius™ also allows chec

Page 81 - READING FEATURES

SOFTWARE CONFIGURATION 3Parameter Default SettingReading Parameters Beam Shutter Disabled Overflow Start Ratio 5 Overflow Stop Ratio 5 Reading Mod

Page 82 - 4.3.1 DS6300 Standard Model

DS6300 3 Parameter Default SettingAuxiliary Serial Port Heartbeat Disable Pass Through Disabled (unchecked) Parameters Baud Rate 115200 Parity

Page 83

READING FEATURES 44 READING FEATURES 4.1 ADVANCED CODE RECONSTRUCTION (ACR™ 4) The traditional way of barcode reading could be called “Linear Read

Page 84

ITALIANO Informazione degli utenti ai sensi della Direttiva Europea 2002/96/EC L’apparecchiatura che riporta il simbolo del bidone barrato deve esse

Page 85 - 110 120 130 140

DS6300 4 The decoder will be able to read the label with a tilt angle between + α max and - α max as shown in the following figure: ConveyorLaser B

Page 86 - Position = 0

READING FEATURES 4 Minimum Code Height for ACR Reading (mm) 45° 30° Conveyor Speed (m/s) 0.5 1 1.5 2 2.5 3 0.5 1 1.5 2 2.5 3 0.25 9 10 12 14 16 1

Page 87

DS6300 4 4.3 READING DIAGRAMS 4.3.1 DS6300 Standard Model DS6300-100-0XX - Resolution: 0.20 mm/8 mils CONDITIONS Code = Interleaved 2/5 or Code

Page 88

READING FEATURES 4DS6300-100-0XX - Resolution: 0.30 mm/12 mils 4 2 0 6 (in) 0 8 14 (in)10 12 16 180 20 25 30 35 40 45 50 55(cm)252015 100 (cm) 5-

Page 89

DS6300 4 DS6300-100-0XX - Resolution: 0.38 mm/15 mils 4 2 06 (in) 0 12 18 (in)14 16 20 220 30 35 40 45 50 55(cm)252015100 (cm) 5-5-10-15-20-258 1

Page 90

READING FEATURES 4DS6300-100-0XX - Resolution: 0.50 mm/20 mils 8 4 0 12 (in) 0 8 20 (in)12 16 24 280 20 30 40 50 60 70 80 90(cm)504030 200 (cm) 1

Page 91

DS6300 4 4.3.2 DS6300 Oscillating Mirror Model DS6300-105-0XX (oscillating mirror) - Resolution: 0.20 mm/8 mils 4 2 0 6 (in) 0 6 12(in) 8 10 14

Page 92 - 5 MAINTENANCE

READING FEATURES 4DS6300-105-0XX (oscillating mirror) - Resolution: 0.30 mm/12 mils 4 2 0 6 (in) 0 8 14 (in)10 12 16 180 20 25 30 35 40 45 50 55(

Page 93 - MAINTENANCE

DS6300 4 DS6300-105-0XX (oscillating mirror) - Resolution: 0.38 mm/15 mils 4 2 06 (in) 0 10 16 (in)12 14 18 200 25 30 35 40 45 50(cm)252015100 (cm

Page 94 - 6 TROUBLESHOOTING

READING FEATURES 4DS6300-105-0XX (oscillating mirror) - Resolution: 0.50 mm/20 mils Focus Position = 60 8 4 0 12 (in) 504030 200 (cm) 10-10-20-30 -

Page 95

GENERAL VIEW DS6300 8 2 1 3 4 5 6 7 Figure A - DS6300 Laser Safety Label Warning and Device Class Label Identification Label Service Cap

Page 96

DS6300 4 4.3.3 DS6300 with GFX-60 DS6300 with GFX-60 - Resolution: 0.20 mm/8 mils Figure 86 – GFX-60 0.20 mm / 8 mils Reading Diagram Note: 0 va

Page 97 - 7 TECHNICAL FEATURES

READING FEATURES 4DS6XXX with GFX-60 - Resolution: 0.50 mm/20 mils Figure 88 - GFX-60 0.50 mm / 20 mils Reading Diagram Note: 0 value on the X axi

Page 98

DS6300 5 5 MAINTENANCE 5.1 CLEANING Clean the laser beam output window (Figure A, 7) periodically for correct operation of the scanner. Dust, dirt

Page 99 - GLOSSARY

MAINTENANCE 55.2.2 Scanner Replacement Procedure NOTE The ASR procedure requires replacing one scanner at a time. Slave 1. Power down the entire

Page 100

DS6300 6 6 TROUBLESHOOTING NOTE Before contacting your local Datalogic office or Datalogic Partner or ARC, it is suggested to save the device confi

Page 101

TROUBLESHOOTING 6TROUBLESHOOTING GUIDE Problem Suggestion On Line Mode and Serial On Line Mode: the reader does not respond correctly to the expected

Page 102

DS6300 6 TROUBLESHOOTING GUIDE Problem Suggestion How do I obtain my units’ serial numbers? • The device serial number is printed on the device ident

Page 103

TECHNICAL FEATURES 77 TECHNICAL FEATURES ELECTRICAL FEATURES (see note 1) Supply voltage 15 to 30 Vdc Power consumption 15 W typical 20 W Max. (in

Page 104 - DECLARATION OF CONFORMITY

DS6300 7 SOFTWARE FEATURES Interleaved 2/5 Code 39 standard Codabar Code 128 EAN128 Code 93 (Standard and Full ASCII) Readable codes EAN/UPC (includi

Page 105

GLOSSARY ACR™ 4 Each version of the base has the powerful code reconstruction technology (ACR™ 4). The new fourth generation ACR considerably incre